Application:
  • Control of the flow of refrigerants during the service.
Description:
  • Features:
  • Records and stores up to 24 hours of data and up to 15 tasks.
  • It has a large, clear LCD display.
  • Displays pressure, saturation temperature, actual temperature, superheating and subcooling.
  • Contains a database of over 60 refrigerants.
  • The thermocouple clamp connector displays the actual temperature and automatically calculates the superheating or subcooling temperature.
  • Vacuum sensor cable displays deep vacuum.
  • The ball valve design includes a 3/8" opening. in the block to increase flow.

Refrigeration factors: R12, R22, R23, R32, R113, R114, R115, R116, R123, R124, R134, R134a, R141B, R142B, R143, R143A, R152A, R290, R401A, R401B, R404A, R407a, R407a, R407a R4 07B, R407C, R407D, R407F, R409A, R410A, R410B, R411A, R411B, R412A, R413A, R414A, R414B, R417A, R422A, R422B, R422C, R422D, R427A, R434A, R43 7A, R438A, R4 41A, R448A, R449A, R452A, R455A, R501, R502, R503, R504, R507A, R508B, R509A, R600, R600A, R601, R601A, R744

New refrigerants can be updated via USB connection and Mastercool software.

Specification:
  • Class 1.0 standard gauge reading
  • Pressure display: PSI, INHg, Bar, MPa, Kg/cm2
  • Temperature display: °F or °C
  • Deep Vacuum Display: Microns, mBar, KPa, Pa, Torr, mTorr, mmHg
  • High resolution: 1 psi (0.07 bar, 0.007 MPa, 0.07 kg/cm2)
  • Sensor Accuracy: 1 psi or 1% of reading (whichever is greater)
  • Working pressure: 0 to 750 psi (52 bar, 5 MPa, 52 kg/cm2) (does not display 0-5 psi)
  • Test pressure: 1000 psi (70 bar, 7 MPa, 70 kg/cm2) (pressure allowed without internal damage)
  • Refrigerant temperature range: -40 to 200°F (-40 to 93°C)
  • Operating temperature: 0 to 45°C (32 to 122°F)
  • Temperature measurement accuracy: ±1oF (±0.5oC) in the range from 32 to 160oF (0 to 71oC)
  • Storage temperature: 10 to 120°F (-12 to 49°C)
  • Connections: 1/4" M-flare
  • Power supply: 9V DC battery with optional AC/DC power supply
  • Battery life: 30-36 hours in pressure and temperature mode only (continuous use) / 25-30 hours in vacuum or backlight mode (continuous use)
  • Auto power off: 15 min. with the option to turn it off
Additional information:


Tag: manometer set, manometers, digital analyzer

Data sheet

Supplier
Mastercool
Type
digital
Number of valves
4
Hoses type
4 x 180 cm